Features
1. The central control unit of EXC9100 all-digital excitation system adopts the streamlined circuit construction with mainstream ARM + new FPGA chip as its core.Technical Parameters
No.
|
Content
|
Provision
|
Performance
|
1
|
Regulators performance indicators
|
Force-excitation ceiling voltage and time
|
100MW steam turbine:1.8 times of the rated voltage.
50MW turbine : 2 times of the rated voltage. The duration of not less than 10S. Ceiling voltage is calculated as 80% of the terminal voltage. |
Voltage response time
|
Less than 0.1S
|
||
The accuracy of the regulator
|
Less than ± 0.5%
|
||
Droop Range
|
Not less than ± 15%
|
||
Frequency and voltage droop change
|
When the frequency change of 1%, the voltage variation is not greater than ± 0.25% of rated
|
||
10% phase step in the condition of no load
|
Voltage overshoot amount of not more than 50% of the step, the oscillation is not more than 3 times, settling time is not greater than 10S
|
||
Excitation field-flashing
|
Voltage overshoot is not more than 15% of rated voltage, the oscillation is not more than 3 times, the adjustment time is not greater than 10S
|
||
Rated load rejection
|
Voltage overshoot is not more than 15% of rated voltage, the oscillation is not more than 3 times, the adjustment time is not greater than 10S
|
||
The adjustment range
|
AVR:70% to 110% rated voltage
FCRl: 20% no-load excitation current to 110% therated excitation current |
||
Given speed
|
0.3%~1%/S
|
||
Nominal response
|
More than 50MW turbine and steam turbine 100MW of not less than two times per second rated excitation voltage, and the rest of not less than 1 times per second rated excitation voltage
|
||
The generator static voltage droop
|
Not more than ± 1%
|
||
2
|
The rectifier bridge
|
Current coefficient
|
Not less than 0.85
|
Rectifier redundancy
|
N-1
|
||
The maximum instantaneous value of the output voltage of the rectifier
|
1.1 times the rated excitation current, shall not exceed the amplitude of the voltage-to-ground voltage of 30%.
|
||
3
|
Inversion and overvoltage protection
|
Deexcitation overvoltage
|
Shall not be less than the factory test voltage to ground voltage amplitude of 30%, shall not exceed 50%.
|
ZNO
|
Chargeability of less than 60%, 20% of the capacity margin.
|
||
4
|
Power supply
|
Operating frequency range
|
45~82.5Hz
|
AC380V/220
|
+10%~-15%
|
||
DC220V/110V
|
-15%~+10%
|
||
5
|
System
|
Forced removal rate of excitation system
|
Not more than 0.2%
|